basseek.blogg.se

Fire sprinkler design flow test
Fire sprinkler design flow test













The centerline of the orifice should be at a right angle to the plane of the face of the hydrant outlet.

  • Record your pitot reading by inserting the orifice of the pitot tube into the center of the flow of water and away from the opening at half the diameter of the opening.
  • This could take several seconds of !ow from the secondary flowing hydrant.
  • Record the residual pressure from the pressure hydrant gauge after the pressure needle stabilizes.
  • Note that it may be necessary to use a diffuser.

    fire sprinkler design flow test

    Completely open the valve on the flowing hydrant, making sure the path of flow to the drain or pathway is safe and clear of debris and obstacles.Note any elevation changes from the pressure hydrant to the structure and the flowing hydrant.Then completely open the valve and take the static pressure reading.

    #Fire sprinkler design flow test install#

    Note: If the hydrant has a ¼-inch outlet to attach pressure gauges (only found on dry-barrel hydrants), remove the plug and install the gauge in the ¼-inch outlet.

  • Remove the nozzle cap on the pressure hydrant and attach a pressure gauge to the outlet.
  • Next, select the subsequent downstream hydrant as the secondary flowing hydrant to obtain your pitot reading. This will be used to gather pressure readings.
  • Locate the test area by choosing the closest hydrant downstream of the building supply line.
  • Hydrant outlet size and type (coefficient of discharge)įollow the steps below to perform a single-hydrant flow test.
  • Flow reading (using pitot gauge) at hydrant A.
  • Residual reading at pressure hydrant B (pressure during flow).
  • Static reading at pressure hydrant B (pressure in the system with no flow).
  • Having a sketch of the site is also a good idea.ĭuring the flow test, be sure to collect the following information: Street pressures can fluctuate s much as 10 psi in the morning compared to the afternoon or night when demand is low. It is best to conduct a flow test during peak hours in the morning to reflect the worst case scenario.

    fire sprinkler design flow test

    While some flow test can involve many hydrants flowing at the same time, the following example uses only one flowing hydrant. Also, ensure that drains are not blocked by leaves or other debris to prevent water backup. A water diffuser and sock can prevent damage to landscaping and roadways as well as redirect water to prevent ice patches on surfaces in the winter. You should have the proper equipment on hand, including a flow test kit with the correct nozzle size to attach to the hydrants. It is important to notify the water company or water authority before conducting any water flow test, since opening the hydrant could disrupt normal operating conditions in the water distribution system in that area. Incorrect readings can result in additional fire pumps for under-designed systems or costly overdesign in pipe sizing. A flow test is required in most jurisdictions and is critical for proper fire sprinkler system design. In addition, it is also necessary to perform a flow test to properly design a fire sprinkler system for a commercial or residential structure. Performing a fire hydrant flow test provides the actual static pressure, residual pressure and the flow from the hydrant. NFPA recommends that a residual pressure of 20 psi be maintained in fire hydrants for them to be effective for firefighting and preventing the contamination of public water supplies by backflow.

    fire sprinkler design flow test

    Fire hydrants are tested regularly to ensure that they are capable of providing water at an acceptable pressure and flow rate foe public health and firefighting operations. Fire hydrant flow test determine the flow rate and pressure in any location through-out a water company’s or water authority’s underground water distribution system.













    Fire sprinkler design flow test